00 items
![201031423186149[1]](https://syslinkcomputers.com/wp-content/uploads/2024/10/2010314231861491-400x330.jpg)

- Description
- Reviews (0)
Description
- Description : Wired Photoelectric Smoke Detector
- Model No : S-SN02
Features
- Newly-developed Infrared photoelectric smoke sensor unit inside;
- Independently or as a front-end detector of an alarm system;
- Wired transmitting digital signal to control panel;
- Intelligent logic control, eliminate false alarm;
- Microcontroller temperature analysis and Automatic temperature compensation for best summertime detection;
- Tightly-mated bug guard to protect the sensor optics from insects, spiders and dust, Worm, it is dustproof, mothproof and anti-white light;
- Strong adaptability to circumstance requirements;
- SMT adopted, RF and EMI Immunity;
- Manual test, auto-reset, and low power consumption;
- Thin structure design;
- Alarm output contacts of relay: N.C./ N.O. optional.
Technical Specifications
Operating Voltage | DC9V-16V |
---|---|
Standby Current | less than 3mA |
Alarm Current | less than 25mA |
RF Immunity | > 20 V/m 10 – 1000 MHz |
Sensitivity class | I, 3%/m |
White Light Immunity | > 8000 lux |
Noise(Vp-p) | <200mV, (mVp-p)(25°C) |
Alarm Output | NC or NO, sound & flash alarm,85dB@1m |
Alarm Volume | 80 square meters (with the installation height of 6m-12m), and 60 square meters (with the |
installation height | of less than 6m) |
Temperature Range | -10°C to +50°C |
Relative Humidity | Less than 95% (25°C) |
Installation Mode | Ceiling Mounted |
Housing | High-impact ABS |
Dimensions | 100mm x 43mm (Dia.xH) |
Applications | For indoor use |
Reviews